Skip to content

KFWA BY

KFWA MAIN per filtrazione carburante separazione acqua trattamento diesel

KFWA BY

The KFWA BY is used for the filtration and separation of fuel oils between the storage tank and the service tank. The system is divided into two parts (pump module/treatment module) to adapt to site conditions. The gear pump sends the fuel to the treatment stage, where it is filtered and separated. The separated water is detected by a probe and automatically discharged.

Applications

The KFWA system is primarily used for separating water from fuel in:

  • medium-to-large vessels;
  • power plants for generating energy from liquid fuels;
  • heating systems;
  • heavy earthmoving machinery.
  • Maximum inlet water content 1,000 ppm.
  • Outlet water concentration 70 ppm.
  • Flow rate 800–8,000 l/h.
  • Maximum ambient temperature 55°C.
  • Maximum fluid temperature 45°C.
  • A wide range of usable operating fluids.
  • Highly efficient water filtration, separation and automatic drainage in a single system.
  • Compact design requires little space.
  • Low operating costs.
  • Low maintenance.
  • The system is inserted between the storage tank and the service tank.
  • The filter’s clogging status is monitored via a differential pressure switch.
  • At a differential pressure of 2.0 bar, the element must be replaced.
  • If replacement is not performed, the bypass valve opens, sending untreated fluid to the engine.